Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 13, 2016, 09:14 AM
  • 05 0713_05 0752 _13102016_021535.mp4

Date
10/13/2016
W/O
591783
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00521
PipeID
P05978
Time
2:14 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3603
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_591783_TV05308_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0713
Downstream MH
05 0752
Dir. of Survey
Downstream
Length Surveyed
344.7 ft.
Total Length
344.7 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 05 0713 to 05 0752
MH: 05 0713MH: 05 0752downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07130 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. MGO - General Observation - LATERAL AT MH 5 O'CLOCK76 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES106.5 ft. CM - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES121.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start302.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish344.7 ft. AMH - Downstream Manhole, Survey Ends - 05 0752

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    76 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    106.5 ft. - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    121.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
76CM
0AMH05 0713
0.1MGOLATERAL AT MH 5 O'CLOCK
106.5CM
121.4CM
344.7AMH05 0752
302.4CM
0MWL
0MWM

Properties (6)

additional_info
SC306198
custom_field_two
3
customer
LACSD
datetime
2016-10-13T02:14:58-07:00
documentation
PROPIPE
is_lateral_inspection
false