Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 18, 2016, 08:54 AM
  • 02 0761_02 0760_20160718_031339.mp4

Date
07/18/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03319
Time
1:54 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3656
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0761
Downstream MH
02 0760
Dir. of Survey
Downstream
Length Surveyed
309.9 ft.
Total Length
309.9 ft.
Structural Index
2
Structural Quick
2400
Structural Rating
8
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 0761 to 02 0760
MH: 02 0761MH: 02 0760downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 07610 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"11.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"59.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"62.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"108 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"111 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"143.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES156.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"160.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"188.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES208.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"211.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"255.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES260.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"263.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"280.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES307 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish309.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0760309.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK

Observation photos (9)

  • Water Mark, 25 %of cross sectional area

    0 ft. - Water Mark, 25 %of cross sectional area

  • Water Level, 15 %of cross sectional area

    0 ft. - Water Level, 15 %of cross sectional area

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    8 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    11.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    59.7 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    143.6 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    188.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    255.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    307 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (23)

DistanceCodeObservation
160.1TFC
111TFC
143.6CL
309.9AMH02 0760
0MWM
8TFC
0AMH02 0761
108TFA
11.2TFC
255.9CL
156.9TFA
208.8TFC
307DAGS
309.9MGOCONNECTION AT THE MH 3 O'CLOCK
188.8CL
0MWL
263.5TFC
2DAGS
260.4TFA
211.9TFC
62.8TFC
280.7CL
59.7TFA

Properties (6)

additional_info
SC305535
custom_field_two
4
customer
LACSD
datetime
2016-07-18T01:54:58-07:00
documentation
PROPIPE
is_lateral_inspection
false