Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2016, 11:17 AM
  • 02 0733_02 0732_20160719_052747.mp4

Date
07/19/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03288
Time
4:17 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3657
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0733
Downstream MH
02 0732
Dir. of Survey
Downstream
Length Surveyed
292.7 ft.
Total Length
292.7 ft.
Structural Index
1
Structural Quick
1100
Structural Rating
1
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 0733 to 02 0732
MH: 02 0733MH: 02 0732downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 07330 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start8.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"16.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"19.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"80.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"133.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"133.8 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 4", 3"223.5 ft. CC - Crack Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES230.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"233.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"274.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"289.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish292.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0732

Observation photos (6)

  • Water Level, 5 %of cross sectional area

    0 ft. - Water Level, 5 %of cross sectional area

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    8.7 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"

    80.9 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 4", 3"

    133.8 ft. - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 4", 3"

  • Crack Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES

    223.5 ft. - Crack Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    274.8 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

Observations (16)

DistanceCodeObservation
133.8TBI
292.7AMH02 0732
0AMH02 0733
274.8TBA
16.8TFA
233.1TFC
80.9TBA
230.7TFA
8.7TBA
223.5CC
133.2TFA
19.5TFC
0MWL
289.5DAGS
2DAGS
0MWM

Properties (6)

additional_info
SC305536
custom_field_two
4
customer
LACSD
datetime
2016-07-19T04:17:00-07:00
documentation
PROPIPE
is_lateral_inspection
false