Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2016, 06:38 PM
  • H 0930_H 0929_20160217_115205.mp4

Date
02/17/2016
W/O
552579
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z01005
PipeID
P15343
Time
10:38 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3182
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
CITY OF INDUSTRY
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
33
Purpose
Routine Assessment
Project
WO_552579_TV21022_FEB2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Upstream MH
H 0930
Downstream MH
H 0929
Dir. of Survey
Downstream
Length Surveyed
468.5 ft.
Total Length
468.5 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
3
O&M Quick
4111
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole H 0930 to H 0929
MH: H 0930MH: H 0929downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 09300 ft. MWM - Water Mark, 55 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAGNEZIUM H.O COATING 50% start465.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish465.7 ft. MGO - General Observation - MAGNEZIUM H.O COATING 50% finish468.5 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH468.5 ft. AMH - Downstream Manhole, Survey Ends - H 0929468.5 ft. VC - Vermin Cockroach468.5 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH

Observations (11)

DistanceCodeObservation
0MWL
468.5MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
468.5AMHH 0929
468.5VC
468.5MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
2SSS
465.7SSS
0AMHH 0930
465.7MGOMAGNEZIUM H.O COATING 50% finish
2MGOMAGNEZIUM H.O COATING 50% start
0MWM

Properties (6)

additional_info
SC224997
custom_field_two
4
customer
LACSD
datetime
2016-02-17T10:38:35-08:00
documentation
PRO PIPE
is_lateral_inspection
false