Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 10, 2018, 11:23 AM
  • 08 0094_08 0093 _10042018_042627.mp4

Date
04/10/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00122
Time
4:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5526
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
01
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0094
Downstream MH
08 0093
Dir. of Survey
Downstream
Length Surveyed
37.8 ft.
Total Length
37.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 08 0094 to 08 0093
MH: 08 0094MH: 08 0093downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00940 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH8.6 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES12.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.8 ft. AMH - Downstream Manhole, Survey Ends - 08 009337.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    8.6 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
12.5CM
37.8AMH08 0093
0MWL
0MWM
8.6CL
0AMH08 0094
37.8CM
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH

Properties (6)

additional_info
SC358733
custom_field_two
3
customer
LACSD
datetime
2018-04-10T04:23:11-07:00
documentation
PROPIPE
is_lateral_inspection
false