Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2018, 07:17 AM
  • 08 0040_08 0039 _13042018_002820.mp4

Date
04/13/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00042
Time
12:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5529
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
08 0039
Downstream MH
08 0040
Dir. of Survey
Upstream
Length Surveyed
67.6 ft.
Total Length
67.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2A00
O&M Rating
22
Overall Index
2
Overall Quick
Overall Rating
25
Pipe schematic from manhole 08 0039 to 08 0040
MH: 08 0039MH: 08 0040upstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 08 00402.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish5.3 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES57 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start67.6 ft. MWL - Water Level, 10 %of cross sectional area67.6 ft. AMH - Downstream Manhole, Survey Begins - 08 003967.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK67.6 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

    62.3 ft. - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
0MWL
67.6MGOCONNECTION AT MH 3 O'CLOCK
65DSZ
0AMH08 0039
0MGOCONNECTION AT MH 3 O'CLOCK
0MWM
67.6AMH08 0040
10.6DSZ
62.3CM

Properties (6)

additional_info
SC358736
custom_field_two
3
customer
LACSD
datetime
2018-04-13T00:17:14-07:00
documentation
PROPIPE
is_lateral_inspection
false