Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2018, 09:48 AM
  • 08 0053_08 0052 _12042018_030011.mp4

Date
04/12/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00055
Time
2:48 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5528
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0053
Downstream MH
08 0052
Dir. of Survey
Downstream
Length Surveyed
324.1 ft.
Total Length
324.1 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 08 0053 to 08 0052
MH: 08 0053MH: 08 0052downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 005325 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES176.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"178.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES228.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"277 ft. TS - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"324.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0052

Observation photos (3)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    167.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    178.4 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    277 ft. - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (12)

DistanceCodeObservation
0MWL
167.7CL
324.1AMH08 0052
0MWM
178.4CL
25TF
228.1TFC
176.6TFC
75.4TFC
126.6TFC
277TS
0AMH08 0053

Properties (6)

additional_info
SC358735
custom_field_two
3
customer
LACSD
datetime
2018-04-12T02:48:55-07:00
documentation
PROPIPE
is_lateral_inspection
false