Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2016, 09:23 AM
  • 02 0372_02 0371 _20160809_033822.mp4

Date
08/09/2016
W/O
252431
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00250
PipeID
P02687
Time
2:23 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3678
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Routine Assessment
Project
WO_252431_TV02049_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0372
Downstream MH
02 0371
Dir. of Survey
Downstream
Length Surveyed
311.8 ft.
Total Length
311.8 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 02 0372 to 02 0371
MH: 02 0372MH: 02 0371downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03722.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start29.3 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES36.8 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES46.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"51 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"61.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES95.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"100.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"101.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - WANDERING140.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"145.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"189.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"197.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"241.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"246.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"304.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish304.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish311.8 ft. MGO - General Observation - STUB 3 O'CLOCK311.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0371311.8 ft. MGO - General Observation - STUB 9 O'CLOCK

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    29.3 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    36.8 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    61.1 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - WANDERING

    101.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - WANDERING

Observations (23)

DistanceCodeObservation
0MWL
311.8MGOSTUB 3 O'CLOCK
100.8TFC
145.4TFA
197.1TFA
29.3CL
304.4CM
311.8AMH02 0371
101.9CMWANDERING
36.8CM
0MWM
2.1DAGS
0AMH02 0372
189.8TFC
46.6TFC
241.7TFC
51TFA
304.4DAGS
61.1CM
95.8TFC
140.1TFC
246.1TFC
311.8MGOSTUB 9 O'CLOCK

Properties (6)

additional_info
SC306008
custom_field_two
4
customer
LACSD
datetime
2016-08-09T02:23:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false