Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2016, 11:42 AM
  • 02 0382_02 0381 _20160808_055454.mp4

Date
08/08/2016
W/O
252431
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00250
PipeID
P02700
Time
4:42 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3677
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_252431_TV02049_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0382
Downstream MH
02 0381
Dir. of Survey
Downstream
Length Surveyed
308 ft.
Total Length
308 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 02 0382 to 02 0381
MH: 02 0382MH: 02 0381downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03820 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.3 ft. VC - Vermin Cockroach14.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"64.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"71.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"95.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"95.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES137.2 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES171.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4"194.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"238.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"239.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES258 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"305.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish308 ft. AMH - Downstream Manhole, Survey Ends - 02 0381308 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE308 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Vermin Cockroach

    9.3 ft. - Vermin Cockroach

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    95.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    137.2 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    239.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
239.6CM
194.6TF
0MWM
305.4DAGS
238.7TFC
258TF
9.3VC
95.9CM
14.4TF
95.2TFC
71.7TF
64.4TF
2DAGS
0AMH02 0382
171.4TF
308AMH02 0381
137.2CM
0MWL
308MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
308MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE

Properties (6)

additional_info
SC306007
custom_field_two
4
customer
LACSD
datetime
2016-08-08T04:42:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false