Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2016, 09:32 AM
  • 02 0362_02 0361 _20160812_034113.mp4

Date
08/12/2016
W/O
252431
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00250
PipeID
P02676
Time
2:32 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3681
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_252431_TV02049_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0362
Downstream MH
02 0361
Dir. of Survey
Downstream
Length Surveyed
263.2 ft.
Total Length
263.2 ft.
Structural Index
1
Structural Quick
1300
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
1
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 0362 to 02 0361
MH: 02 0362MH: 02 0361downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 036228.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"203.7 ft. CC - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES210.4 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES247.4 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES263.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE263.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0361

Observation photos (3)

  • Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES

    203.7 ft. - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

    210.4 ft. - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES

    247.4 ft. - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
263.2AMH02 0361
247.4CC
210.4CC
0MWM
0MWL
28.1TFA
0AMH02 0362
263.1MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
203.7CC

Properties (6)

additional_info
SC306011
custom_field_two
4
customer
LACSD
datetime
2016-08-12T02:32:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false