Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2016, 09:45 AM
  • 02 0394_02 0393A _20160810_035404.mp4

Date
08/10/2016
W/O
252431
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00250
PipeID
P25733
Time
2:45 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3679
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
PARAMOUNT, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Routine Assessment
Project
WO_252431_TV02049_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0393A
Downstream MH
02 0394
Dir. of Survey
Upstream
Length Surveyed
243.8 ft.
Total Length
243.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 0393A to 02 0394
MH: 02 0393AMH: 02 0394upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 03940 ft. MGO - General Observation - STUB 9 O'CLOCK0 ft. MGO - General Observation - STUB 3 O'CLOCK1.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish87.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"92 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"133.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"138.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"195.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"200.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"242.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"242.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start243.8 ft. AMH - Downstream Manhole, Survey Begins - 02 0393A243.8 ft. MWL - Water Level, 10 %of cross sectional area243.8 ft. MWM - Water Mark, 30 %of cross sectional area243.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    242.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (16)

DistanceCodeObservation
1.6TFC
0AMH02 0393A
0MWL
242.1DAGS
105.5TFC
110.3TFA
48.1TFC
156.4TFC
243.8AMH02 0394
0MWM
243.8MGOSTUB 9 O'CLOCK
151.8TFC
0MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
43.3TFC
243.8MGOSTUB 3 O'CLOCK
1.6DAGS

Properties (6)

additional_info
SC306009
custom_field_two
4
customer
LACSD
datetime
2016-08-10T02:45:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false