Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2016, 05:59 AM
  • 02 0378A_02 0378 _20160809_001832.mp4

Date
08/08/2016
W/O
252431
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00250
PipeID
P02695
Time
10:59 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3678
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_252431_TV02049_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0378A
Downstream MH
02 0378
Dir. of Survey
Downstream
Length Surveyed
299.3 ft.
Total Length
299.3 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 02 0378A to 02 0378
MH: 02 0378AMH: 02 0378downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 0378A0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE50.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES57 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"64.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"104.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"111.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"147.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"155.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"190.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"202.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4"242 ft. RMC - Roots Medium Connection, at 02 o'clock, 10 %, within 8 inches of joint: YES242 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"257.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"282.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"294.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES299.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0378

Observation photos (3)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    50.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Roots Medium Connection, at 02 o'clock, 10 %, within 8 inches of joint: YES

    242 ft. - Roots Medium Connection, at 02 o'clock, 10 %, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    294.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
0MWM
0AMH02 0378A
299.3AMH02 0378
0MWL
57TFC
104.6TFC
190.6TFC
257.9TFA
155.1TF
294.9CM
242RMC
202.1TFC
50.9CM
147.8TFA
0MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
0MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
111.9TFC
242TFA
282.2TFC
64.3TFA

Properties (6)

additional_info
SC306008
custom_field_two
4
customer
LACSD
datetime
2016-08-08T22:59:24-07:00
documentation
PRO-PIPE
is_lateral_inspection
false