Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2016, 05:59 AM
  • 02 0394B_02 0394A _20160812_000517.mp4

Date
08/11/2016
W/O
252431
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00250
PipeID
P02716
Time
10:59 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3681
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
PARAMOUNT, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Routine Assessment
Project
WO_252431_TV02049_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0394B
Downstream MH
02 0394A
Dir. of Survey
Downstream
Length Surveyed
204.6 ft.
Total Length
204.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 0394B to 02 0394A
MH: 02 0394BMH: 02 0394Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 0394B0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE6.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start21.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"27 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"59.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4"73.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"78.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"119.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"125.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"161.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"167 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"201.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES201.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish204.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE204.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0394A

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    59.5 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    167 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    201.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    201.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (18)

DistanceCodeObservation
0MWL
59.5TB
73.2TFC
204.6MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
119.8TFC
0AMH02 0394B
21.7TFC
201.3CM
167TFC
125.4TF
201.3DAGS
161.7TFC
0MWM
6.1DAGS
0MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
78.7TFC
204.6AMH02 0394A
27TFC

Properties (6)

additional_info
SC306011
custom_field_two
4
customer
LACSD
datetime
2016-08-11T22:59:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false