Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2017, 08:52 PM
  • 02 2376_02 2375 _03232017_150321.mp4

Date
03/23/2017
W/O
1590881
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00279
PipeID
P21005
Time
1:52 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4323
Sewer Name
02 MONTEBELLO TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_624375_TV02084_MAR20172
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 2376
Downstream MH
02 2375
Dir. of Survey
Downstream
Length Surveyed
241.1 ft.
Total Length
241.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2R00
O&M Rating
188
Overall Index
2
Overall Quick
Overall Rating
188
Pipe schematic from manhole 02 2376 to 02 2375
MH: 02 2376MH: 02 2375downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 23760 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start37 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"58.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"119 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"165 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"227.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4"231.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"241 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish241 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish241.1 ft. AMH - Upstream Manhole, Survey Ends - 02 2375

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    6 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
37TF
6DAE
165TF
0AMH02 2376
6DAGS
227.1TF
241DAGS
58.1TF
119TF
231.1TF
241DAE
241.1AMH02 2375
0MWL
0MWM

Properties (7)

additional_info
SC318738
custom_field_two
4
customer
LACSD
datetime
2017-03-23T13:52:36-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
34415