Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2017, 08:52 PM
  • 02 0995_02 0994A _03232017_140951.mp4

Date
03/23/2017
W/O
1590881
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00279
PipeID
P03568
Time
1:52 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4323
Sewer Name
02 MONTEBELLO TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
WO_624375_TV02084_MAR20172
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0995
Downstream MH
02 0994A
Dir. of Survey
Downstream
Length Surveyed
40 ft.
Total Length
40 ft.
Structural Index
3
Structural Quick
3700
Structural Rating
21
O&M Index
2
O&M Quick
2700
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
35
Pipe schematic from manhole 02 0995 to 02 0994A
MH: 02 0995MH: 02 0994Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 09950 ft. MWL - Water Level, 10 %of cross sectional area3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish40 ft. AMH - Downstream Manhole, Survey Ends - 02 0994A40 ft. MGO - General Observation - CONNECTION AT 4 O'CLOCK40 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
40DAGS
0AMH02 0995
40AMH02 0994A
5.1CM
40MGOCONNECTION AT 4 O'CLOCK
3.1DAGS
40CM
0MWL

Properties (6)

additional_info
SC318738
custom_field_two
3
customer
LACSD
datetime
2017-03-23T13:52:35-07:00
documentation
PROPIPE
is_lateral_inspection
false