Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2017, 07:06 AM
  • F 0072B_F 0072A _09142017_000739.mp4

Date
09/14/2017
W/O
651629
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00035
PipeID
P10161
Time
12:06 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4971
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
BELLFLOWER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_651629_TV02199_AUG2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
F 0072B
Downstream MH
F 0072A
Dir. of Survey
Downstream
Length Surveyed
162.1 ft.
Total Length
162.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole F 0072B to F 0072A
MH: F 0072BMH: F 0072Adownstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 0072B0 ft. MWL - Water Level, 35 %of cross sectional area10 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start10 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start33.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"161.8 ft. MGO - General Observation - CONNECTION AT 9 OCLOCK, ACTIVE161.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish162 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish162.1 ft. AMH - Downstream Manhole, Survey Ends - F 0072A

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    10 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
10SAP
33.3TF
161.9DAGS
162SAP
0MWM
0AMHF 0072B
10DAGS
0MWL
162.1AMHF 0072A
161.8MGOCONNECTION AT 9 OCLOCK, ACTIVE

Properties (6)

additional_info
SC345963
custom_field_two
3
customer
LACSD
datetime
2017-09-14T00:06:02-07:00
documentation
PROPIPE
is_lateral_inspection
false