Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2016, 06:17 AM
  • 02 2272_02 2271_20161019_233218.mp4

Date
10/19/2016
W/O
597387
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00290
PipeID
P04523
Time
11:17 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3743
Sewer Name
02 MONTEREY PARK EXTENSION RELIEF TRUNK
City
MONTEREY PARK, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
06
Purpose
Routine Assessment
Project
WO_597387_TV02101_OCT2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 2272
Downstream MH
02 2271
Dir. of Survey
Downstream
Length Surveyed
467.4 ft.
Total Length
467.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2Q11
O&M Rating
185
Overall Index
2
Overall Quick
Overall Rating
185
Pipe schematic from manhole 02 2272 to 02 2271
MH: 02 2272MH: 02 2271downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 22720 ft. MWL - Water Level, 20 %of cross sectional area0 ft. VC - Vermin Cockroach3.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start465.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish467.4 ft. AMH - Downstream Manhole, Survey Ends - 02 2271

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWM
465.8DAGS
0AMH02 2272
3.3DAGS
0MWL
467.4AMH02 2271
0VC

Properties (7)

additional_info
SC303733
custom_field_two
4
customer
LACSD
datetime
2016-10-19T23:17:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
32490