Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2016, 06:38 AM
  • 02 2348_02 2347_20161018_235115.mp4

Date
10/18/2016
W/O
597387
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00290
PipeID
P20979
Time
11:38 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3743
Sewer Name
02 MONTEREY PARK EXTENSION RELIEF TRUNK
City
MONTEREY PARK, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_597387_TV02101_OCT2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 2348
Downstream MH
02 2347
Dir. of Survey
Downstream
Length Surveyed
300.2 ft.
Total Length
300.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
2
Overall Quick
Overall Rating
118
Pipe schematic from manhole 02 2348 to 02 2347
MH: 02 2348MH: 02 2347downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 23480 ft. MWL - Water Level, 30 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start56.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"120.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"279.1 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"297.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish300.2 ft. AMH - Downstream Manhole, Survey Ends - 02 2347

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    56.6 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

Observations (9)

DistanceCodeObservation
0MWM
300.2AMH02 2347
120.8TFA
0AMH02 2348
56.6TBA
297.8DAGS
0MWL
279.1TFA
2.2DAGS

Properties (7)

additional_info
SC303732
custom_field_two
4
customer
LACSD
datetime
2016-10-18T23:38:16-07:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
33533