Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2016, 09:04 AM
  • 02 1782_02 1781 _25072016_020525.mp4

Date
07/25/2016
W/O
582912
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00275
PipeID
P04132
Time
2:04 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3621
Sewer Name
02 INDIANA STREET RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
07A
Purpose
Routine Assessment
Project
WO_582912_TV02067_JULY2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1782
Downstream MH
02 1781
Dir. of Survey
Downstream
Length Surveyed
227.4 ft.
Total Length
227.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2Z00
O&M Rating
270
Overall Index
2
Overall Quick
Overall Rating
270
Pipe schematic from manhole 02 1782 to 02 1781
MH: 02 1782MH: 02 1781downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 17820 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start225.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish225.4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish225.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish225.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE227.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1781

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Settled Other,  10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0.9 ft. - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    225.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
0MWL
225.4DAGS
0.9DSZ
0AMH02 1782
2DAE
2DAGS
0MWM
225.4DSZ
227.4AMH02 1781
225.4DAE
0MGOCOCKROACHES IN MANHOLE
225.4MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC305800
custom_field_two
4
customer
LACSD
datetime
2016-07-25T02:04:51-07:00
documentation
PRO PIPE
is_lateral_inspection
false