Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2016, 10:46 AM
  • 15 0978_15 0977_31032016_034656.mp4

Date
03/31/2016
W/O
563410
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00636
PipeID
P12753
Time
3:46 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3302
Sewer Name
15 VALINDA TRUNK
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_563410_TV15038_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
15 0977
Downstream MH
15 0978
Dir. of Survey
Upstream
Length Surveyed
348 ft.
Total Length
348 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
138
Pipe schematic from manhole 15 0977 to 15 0978
MH: 15 0977MH: 15 0978upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 15 09781.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE1.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish62.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"118.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"235.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"287.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"338.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"346 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start348 ft. AMH - Downstream Manhole, Survey Begins - 15 0977348 ft. MWM - Water Mark, 40 %of cross sectional area348 ft. MGO - General Observation - COCKROACHES IN MANHOLE348 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK348 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    346.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
60.8TFC
229.5TFC
348MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH15 0977
285.4TFC
168.3TFC
348AMH15 0978
0MWM
346.6MGOCOCKROACHES IN MANHOLE
346.6DAGS
0MGOCOCKROACHES IN MANHOLE
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWL
2DAGS
9.7TFC
112.4TF

Properties (6)

additional_info
SC305428
custom_field_two
4
customer
LACSD
datetime
2016-03-31T03:46:39-07:00
documentation
PRO PIPE
is_lateral_inspection
false