Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2016, 11:08 AM
  • 15 0979_15 0978A_31032016_040844.mp4

Date
03/31/2016
W/O
563410
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00636
PipeID
P25060
Time
4:08 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3302
Sewer Name
15 VALINDA TRUNK
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_563410_TV15038_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
15 0978A
Downstream MH
15 0979
Dir. of Survey
Upstream
Length Surveyed
220.2 ft.
Total Length
220.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412H
O&M Rating
92
Overall Index
2
Overall Quick
Overall Rating
92
Pipe schematic from manhole 15 0978A to 15 0979
MH: 15 0978AMH: 15 0979upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 15 09790 ft. MGO - General Observation - COCKROACHES IN MANHOLE2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish33.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"98.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"220.2 ft. MWL - Water Level, 15 %of cross sectional area220.2 ft. AMH - Downstream Manhole, Survey Begins - 15 0978A220.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE220.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK220.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start220.2 ft. MWM - Water Mark, 50 %of cross sectional area

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    220.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
217.5DAGS
187.1TFC
121.3TFC
220.2MGOACTIVE CONNECTION AT MH 3 O'CLOCK
60.6TFC
0MWL
0AMH15 0978A
0MGOCOCKROACHES IN MANHOLE
220.2AMH15 0979
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0DAGS
220.2MGOCOCKROACHES IN MANHOLE
0MWM

Properties (6)

additional_info
SC305428
custom_field_two
4
customer
LACSD
datetime
2016-03-31T04:08:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false