Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2016, 12:19 PM
  • 15 0980_15 0979_29032016_051916.mp4

Date
03/29/2016
W/O
563410
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00636
PipeID
P12755
Time
5:19 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3299
Sewer Name
15 VALINDA TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_563410_TV15038_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
15 0980
Downstream MH
15 0979
Dir. of Survey
Downstream
Length Surveyed
302.6 ft.
Total Length
302.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
2
Overall Quick
Overall Rating
120
Pipe schematic from manhole 15 0980 to 15 0979
MH: 15 0980MH: 15 0979downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 15 09800 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start56.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"227 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"250.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"300.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE300.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish302.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK302.6 ft. AMH - Downstream Manhole, Survey Ends - 15 0979

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    300.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
167.3TFC
56.2TFC
227TFC
302.6MGOACTIVE CONNECTION AT MH 9 O'CLOCK
250.1TFC
300.5MGOCOCKROACHES IN MANHOLE
0MWL
302.6AMH15 0979
107.4TFC
0MGOCOCKROACHES IN MANHOLE
0AMH15 0980
2DAGS
0MWM
300.5DAGS

Properties (6)

additional_info
SC305425
custom_field_two
4
customer
LACSD
datetime
2016-03-29T05:19:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false