Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2016, 09:54 AM
  • 15 0985_15 0984_29032016_025532.mp4

Date
03/29/2016
W/O
563410
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00636
PipeID
P12760
Time
2:54 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3299
Sewer Name
15 VALINDA TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_563410_TV15038_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
15 0985
Downstream MH
15 0984
Dir. of Survey
Downstream
Length Surveyed
310.1 ft.
Total Length
310.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
122
Pipe schematic from manhole 15 0985 to 15 0984
MH: 15 0985MH: 15 0984downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 15 09842 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start47.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"214.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"308.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish308.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE310.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0984310.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    308.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
102.9TFC
47.6TFC
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
0MWL
310.1AMH15 0984
0MGOCOCKROACHES IN MANHOLE
266.1TFC
310.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
146.1TFC
308.1DAGS
0AMH15 0984
2DAGS
214.3TFC
308.1MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC305425
custom_field_two
4
customer
LACSD
datetime
2016-03-29T02:54:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false