Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2015, 09:34 AM
  • 02 1278_02 1616_20151215013448.mp4

Date
12/15/2015
W/O
521098
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00238
PipeID
P03793
Time
1:34 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2850
Sewer Name
02 BELVEDERE TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_521098_TV02329_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 1278
Downstream MH
02 1616
Dir. of Survey
Downstream
Length Surveyed
79.5 ft.
Total Length
79.5 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
45
O&M Index
2
O&M Quick
2E00
O&M Rating
60
Overall Index
2
Overall Quick
Overall Rating
105
Pipe schematic from manhole 02 1278 to 02 1616
MH: 02 1278MH: 02 1616downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12780 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ROACHES IN MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start78 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish78 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish78.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish79.5 ft. AMH - Downstream Manhole, Survey Ends - 02 161679.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWM
78CM
79.5AMH02 1616
79.5MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0AMH02 1278
0MWL
78DAE
2DAGS
78.1DAGS
2CM
0MGOROACHES IN MH
2DAE

Properties (6)

additional_info
SC204184
custom_field_two
3
customer
LACSD
datetime
2015-12-15T01:34:30-08:00
documentation
PRO PIPE
is_lateral_inspection
false