Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2015, 06:29 AM
  • 02 1306_02 1305A_29102015_232919.mp4

Date
10/29/2015
W/O
521098
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00238
PipeID
P03826
Time
11:29 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2819
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_521098_TV02329_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1306
Downstream MH
02 1305A
Dir. of Survey
Downstream
Length Surveyed
156.2 ft.
Total Length
156.2 ft.
Structural Index
4
Structural Quick
5132
Structural Rating
11
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole 02 1306 to 02 1305A
MH: 02 1306MH: 02 1305Adownstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 13060 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start11.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.9 ft. HVV - Hole Void Visible, from 12 to 02 o'clock, within 8 inches of joint: YES68.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish154.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish156.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1305A156.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK156.2 ft. MGO - General Observation - ROACHES IN MH

Observation photos (2)

  • Hole Void Visible, from 12 to 02 o'clock, within 8 inches of joint: YES

    66.9 ft. - Hole Void Visible, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    68.6 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH02 1306
86.2TFA
154.4DAGS
0MWL
68.6TFD
0MGOCOCKROACHES IN MANHOLE
30.4TFC
11.9CM
156.2AMH02 1305A
0MWM
2DAGS
156.2MGOACTIVE CONNECTION AT MH 9 O'CLOCK
156.2MGOROACHES IN MH
154.4CM
66.9HVV

Properties (6)

additional_info
SC204151
custom_field_two
2
customer
LACSD
datetime
2015-10-29T23:29:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false