Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2017, 10:53 AM
  • 15 0022_15 0021 _02112017_035400.mp4

Date
11/02/2017
W/O
668687
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00622
PipeID
P11911
Time
3:53 AM
Certificate
07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4841
Sewer Name
15 PUENTE TRUNK
City
LA PUENTE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_668687_TV15206_NOV2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
15 0021
Downstream MH
15 0022
Dir. of Survey
Upstream
Length Surveyed
463.1 ft.
Total Length
463.2 ft.
Structural Index
4
Structural Quick
4D3B
Structural Rating
145
O&M Index
2
O&M Quick
2P00
O&M Rating
170
Overall Index
3
Overall Quick
Overall Rating
315
Pipe schematic from manhole 15 0021 to 15 0022
MH: 15 0021MH: 15 0022upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 00222.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish14.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"17.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES34.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"64.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"100.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"130.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"139.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"175.9 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: NO, Finish181.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"201.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"206.3 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: NO, Start213.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES232 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"247.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"249.8 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"257.9 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: NO, Finish282.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"308.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"334.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"343.8 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: NO, Start343.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Finish354.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"369.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"405.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"426.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Start429 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start430.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"463.2 ft. MWM - Water Mark, 20 %of cross sectional area463.2 ft. AMH - Downstream Manhole, Survey Begins - 150021463.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK463.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK463.2 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    34.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Start

    37 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Start

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: NO, Start

    119.4 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: NO, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    249.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: NO, Start

    256.9 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: NO, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    445.8 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (34)

DistanceCodeObservation
323.4TF
108.4TFC
215.5TFC
57.7TFC
0MWM
213.4TB
261.5TFC
129TFC
37FL
332.5TF
231.2TF
119.4FM
398.3TFC
0AMH150021
256.9FM
0MGOCONNECTION AT MH 3 O'CLOCK
281.5TF
119.4FL
180.6TF
445.8CL
463.2AMH15 0022
249.8FL
154.5TFC
287.3FM
34.2DAGS
93.7TF
0MGOCONNECTION AT MH 9 O'CLOCK
449.1TFC
0MWL
205.3FM
363TF
32.9TF
460.8DAGS
428.6TF

Properties (5)

additional_info
SC343947
custom_field_two
3
customer
LACSD
datetime
2017-11-02T03:53:52-07:00
is_lateral_inspection
false