Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2017, 10:56 AM
  • 04 0124_04 0123 _10202017_035940.mpg

Date
10/20/2017
W/O
663608
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00412
PipeID
P11791
Time
3:56 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4751
Sewer Name
04 LA CIENEGA BOULEVARD TRUNK
City
WEST HOLLYWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
WO_663608_TV04007_OCT2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0124
Downstream MH
04 0123
Dir. of Survey
Downstream
Length Surveyed
301.8 ft.
Total Length
301.8 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 04 0124 to 04 0123
MH: 04 0124MH: 04 0123downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 04 01242 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"8.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"12.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"32.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"36.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"84.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"90.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"251.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"277.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.4 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR301.8 ft. AMH - Downstream Manhole, Survey Ends - 04 0123, CONNECTION NODE.301.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"301.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

    292.4 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

Observations (24)

DistanceCodeObservation
90.6TFA
5.7TFC
251.5TFA
301.8AMH04 0123, CONNECTION NODE.
0MWM
153.1TFA
2CM
277.1TFA
301.8TFA
32.1TFA
292.4RFJ
2DAGS
0MWL
36.6TFA
228.2TFA
0AMH04 0124
301.8CM
74.4TFA
182.9TFA
12.8TFC
114.8TFA
84.3TFA
8.6TFC
301.8DAGS

Properties (5)

additional_info
SC346064
custom_field_two
3
customer
LACSD
datetime
2017-10-20T03:56:08-07:00
is_lateral_inspection
false