Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2016, 06:33 AM
  • 01 0260_01 0259_062116_233421.mpg

Date
06/21/2016
W/O
574241
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01306
Time
11:33 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3403
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_574241_TV01204_JUNE2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
15 in.
Upstream MH
01 0260
Downstream MH
01 0259
Dir. of Survey
Downstream
Length Surveyed
316 ft.
Total Length
316 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
186
Pipe schematic from manhole 01 0260 to 01 0259
MH: 01 0260MH: 01 0259downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 02603 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES4.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start95.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"137.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"176 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"309.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316 ft. AMH - Downstream Manhole, Survey Ends - 01 0259

Observation photos (2)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    3 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
95.9TF
176TFC
252.3TF
0MWM
309.9CM
0MWL
4.9CM
0MGOCONNECTION AT THE MH 3 O'CLOCK
3CM
316AMH01 0259
210.8TFA
137.3TF
0AMH01 0260

Properties (5)

additional_info
SC305853
custom_field_two
3
customer
LACSD
datetime
2016-06-21T23:33:45-07:00
is_lateral_inspection
false