Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2017, 11:50 PM
  • 18 0827_18 0826 _30082017_162624.mp4

Date
07/26/2017
W/O
651582
Weather
Dry
Operator/Surveyor
COREY D
Sewer ID
Z00707
PipeID
P14690
Time
4:50 PM
Certificate
U-912-159863
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4783
Sewer Name
18 SO WHITTIER OUTFALL TR, SECT 5
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
WO_651582_TV18113_AUG2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0827
Downstream MH
18 0826
Dir. of Survey
Downstream
Length Surveyed
95.6 ft.
Total Length
95.6 ft.
Structural Index
3
Structural Quick
413B
Structural Rating
55
O&M Index
2
O&M Quick
2C00
O&M Rating
36
Overall Index
3
Overall Quick
Overall Rating
91
Pipe schematic from manhole 18 0827 to 18 0826
MH: 18 0827MH: 18 0826downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08270 ft. MWL - Water Level, 10 %of cross sectional area4.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5 ft. FM - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES7.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES14.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start32.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"35.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"81.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"85.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"92.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish92.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish95.1 ft. MGO - General Observation - CONNECTION AT MH95.6 ft. AMH - Downstream Manhole, Survey Begins - 18 0826

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    5 ft. - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    7.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    14.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
4.1DAGS
32.1TF
95.1MGOCONNECTION AT MH
0MWM
85.1TFC
92.1DAGS
92.1CM
5FM
95.6AMH18 0826
35.1TFC
81.1TFC
14.1CM
7.1CM
0AMH18 0827
0MWL

Properties (6)

additional_info
SC344613
custom_field_two
3
customer
LACSD
datetime
2017-07-26T16:50:44-07:00
documentation
PROPIPE
is_lateral_inspection
false