Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 18, 2017, 08:43 AM
  • B 0418_B 0417_1182017_005312.mp4

Date
01/18/2017
W/O
0607729
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00092
PipeID
P08930
Time
12:43 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0398
Sewer Name
B JOINT OUTFALL B - UNIT 5B
City
SIERRA MADRE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
03
Purpose
Routine Assessment
Project
20170113MDM_JOINT_OUTFALL_B_UNIT_5B
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
B 0418
Downstream MH
B 0417
Dir. of Survey
Downstream
Length Surveyed
434.5 ft.
Total Length
434.5 ft.
Structural Index
3
Structural Quick
3B2B
Structural Rating
76
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
76
Pipe schematic from manhole B 0418 to B 0417
MH: B 0418MH: B 0417downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active10.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT10.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT26.1 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - HAIRLINE26.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H42.8 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H46.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H54.4 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H83.2 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H100.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open105.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H105.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H110.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H114.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL126.6 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H175.3 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H183.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H184.9 ft. MGO - General Observation - 21" VCP184.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active219.2 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H231.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H235.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H239.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H255.8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H269.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open283.4 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H287.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H308 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H309.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open334.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H339.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H359.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H363.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H388.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H396.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H416.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H434 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active434.5 ft. AMH - Downstream Manhole, Survey Ends - 1:30AM

Observation photos (1)

  • General Observation - 21" VCP

    184.9 ft. - General Observation - 21" VCP

Observations (41)

DistanceCodeObservation
54.4FCH
183.5FLH
0MWL
434.5AMH1:30AM
83.2FCH
359.5FCH
219.2FCH
231.9FLH
235.3FCH
100.5TFOpen
105.7FLH
114.3FCSL
239.2FCH
339.6FLH
287.4FCH
0MWM
184.9MGO21" VCP
42.8FCH
416.7FLH
10.7FLSLIGHT
26.1FLHAIRLINE
269.6TFOpen
309.2TFOpen
434MGOConn. @ Mh, 3 O' Clock. Active
334.9FCH
46.1FLH
363.6FLH
308FLH
175.3FCH
184.9TFActive
0AMH12:45AM
396.1FLH
105.7FLH
283.4FCH
388.3FLH
0MGOConn. @ Mh, 3 O' Clock. Active
110.6FLH
26.1FCH
10.7FLSLIGHT
126.6FCH
255.8FLH

Properties (6)

custom_field_three
LOTS OF HAIRLINES
custom_field_two
4
customer
LACSD
datetime
2017-01-18T00:43:53-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false