Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2017, 09:14 AM
  • B 0423_B 0422_1132017_041736.mp4

Date
01/13/2017
W/O
0607729
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00092
PipeID
P08935
Time
1:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0394
Sewer Name
B JOINT OUTFALL B - UNIT 5B
City
SIERRA MADRE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
03
Purpose
Routine Assessment
Project
20170113MDM_JOINT_OUTFALL_B_UNIT_5B
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
B 0423
Downstream MH
B 0422
Dir. of Survey
Downstream
Length Surveyed
386 ft.
Total Length
386 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole B 0423 to B 0422
MH: B 0423MH: B 0422downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MWM - Water Mark, 30 %of cross sectional area46.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT77.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped181.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped240.2 ft. MGO - General Observation - 21" VCP263.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped326.2 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H355.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped386 ft. AMH - Downstream Manhole, Survey Ends - 4:45AM

Observation photos (1)

  • General Observation - 21" VCP

    240.2 ft. - General Observation - 21" VCP

Observations (11)

DistanceCodeObservation
0MWL
326.2FCH
386AMH4:45AM
181.8TFCCapped
0AMH4:20AM
77.3TFCCapped
0MWM
46.6FLSLIGHT
263.2TFCCapped
240.2MGO21" VCP
355.8TFCCapped

Properties (4)