Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2017, 06:38 AM
  • 17 0084_17 0083 _14082017_233832.mp4

Date
08/14/2017
W/O
646484
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00669
PipeID
P13802
Time
11:38 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4780
Sewer Name
17 LINCOLN AVENUE TRUNK
City
ALTADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
03
Purpose
Routine Assessment
Project
WO_646484_TV17006_JUL2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
17 0084
Downstream MH
17 0083
Dir. of Survey
Downstream
Length Surveyed
265.3 ft.
Total Length
265.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
1
Overall Quick
Overall Rating
2
Pipe schematic from manhole 17 0084 to 17 0083
MH: 17 0084MH: 17 0083downstream0 ft. AMH - Upstream Manhole, Survey Begins - 17 00840 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area17.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"23.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"23.3 ft. RFC - Roots Fine Connection, from 08 to 10 o'clock37.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"152.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"176.7 ft. RFL - Roots Fine Lateral, at 09 o'clock176.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"265.3 ft. AMH - Downstream Manhole, Survey Ends - 17 0083

Observation photos (1)

  • Roots Fine Connection, from 08 to 10 o'clock

    23.3 ft. - Roots Fine Connection, from 08 to 10 o'clock

Observations (12)

DistanceCodeObservation
37.2TF
176.7RFL
265.3AMH17 0083
0AMH17 0084
0MWL
23.3TF
152.9TF
0MWM
23.3RFC
101.6TF
176.7TF
17.3TF

Properties (7)

additional_info
SC345540
custom_field_two
4
customer
LACSD
datetime
2017-08-14T23:38:11-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP