Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2017, 07:00 AM
  • 17 0082_17 0081 _15082017_000050.mp4

Date
08/15/2017
W/O
646484
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00669
PipeID
P13800
Time
12:00 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4780
Sewer Name
17 LINCOLN AVENUE TRUNK
City
ALTADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
03
Purpose
Routine Assessment
Project
WO_646484_TV17006_JUL2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
17 0082
Downstream MH
17 0081
Dir. of Survey
Downstream
Length Surveyed
244.1 ft.
Total Length
244.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 17 0082 to 17 0081
MH: 17 0082MH: 17 0081downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 17 00820 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK23.7 ft. TFB - Tap Factory Made Abandoned, at 03 o'clock, -, within 8 inches of joint: NO, 6"71.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"95.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"116.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"179.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"182.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"244.1 ft. AMH - Downstream Manhole, Survey Ends - 17 0081

Observations (11)

DistanceCodeObservation
71.8TF
0MWM
0AMH17 0082
182.4TF
244.1AMH17 0081
0MWL
116.6TF
23.7TFB
95.5TF
179.7TF
0MGOCONNECTION AT MH 9 OCLOCK

Properties (7)

additional_info
SC345540
custom_field_two
4
customer
LACSD
datetime
2017-08-15T00:00:27-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
PEP-Deformed/Reformed