Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2016, 06:40 AM
  • 18 0918_18 0917_062316_234128.mpg

Date
06/23/2016
W/O
574406
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00709
PipeID
P14770
Time
11:40 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3405
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
WO_574406_TV18102_JUNE2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Upstream MH
18 0918
Downstream MH
18 0917
Dir. of Survey
Downstream
Length Surveyed
257.9 ft.
Total Length
257.9 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
135
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
135
Pipe schematic from manhole 18 0918 to 18 0917
MH: 18 0918MH: 18 0917downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 5 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 18 09180 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 75%33.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start257.6 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK257.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish257.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0917

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    33.4 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
257.6MGOCONNECTION AT THE MH 3 O'CLOCK
2MGOMAG COAT 75%
0MWM
0MGOCONNECTION AT THE MH 5 O'CLOCK
257.6SAV
257.9AMH18 0917
33.4SAV
0AMH18 0918
0MWL

Properties (6)

additional_info
SC305855
custom_field_two
3
customer
LACSD
datetime
2016-06-23T23:40:54-07:00
documentation
PROPIPE
is_lateral_inspection
false