Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 28, 2017, 07:10 AM
  • H 0791_H 0790A _20170428_005652.mp4

Date
04/28/2017
W/O
635495
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00942
PipeID
P23091
Time
12:10 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4517
Sewer Name
H JOINT OUTFALL H - UNIT 9C
City
SAN DIMAS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
WO_635495_TV22079_MAY2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
20 in.
Width
20 in.
Upstream MH
H 0791
Downstream MH
H 0790A
Dir. of Survey
Downstream
Length Surveyed
198.6 ft.
Total Length
198.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
4131
O&M Rating
7
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole H 0791 to H 0790A
MH: H 0791MH: H 0790Adownstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Downstream Manhole, Survey Begins - H 07912.5 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start31.8 ft. LL - Alignment Left, 25 %, Start111.4 ft. LL - Alignment Left, 25 %, Finish198.6 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish198.6 ft. MSA - Survey Abandoned - CABLE MAXED OUT

Observation photos (2)

  • Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Alignment Left, 25 %, Start

    31.8 ft. - Alignment Left, 25 %, Start

Observations (8)

DistanceCodeObservation
2.5DAGS
198.6DAGS
111.4LL
198.6MSACABLE MAXED OUT
0MWM
31.8LL
0MWL
0AMHH 0791

Properties (6)

additional_info
SC340731
custom_field_two
5
customer
LACSD
datetime
2017-04-28T00:10:53-07:00
documentation
PROPIPE
is_lateral_inspection
false