Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 21, 2017, 09:47 AM
  • 01 0429_01 0428_21032017_024752.mpg

Date
03/21/2017
W/O
624631
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00208
PipeID
P00910
Time
2:47 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4389
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_624631_TV01248_MAR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0428
Downstream MH
01 0429
Dir. of Survey
Upstream
Length Surveyed
156.9 ft.
Total Length
157 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
93
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
93
Pipe schematic from manhole 01 0428 to 01 0429
MH: 01 0428MH: 01 0429upstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 01 04290 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"26.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"31.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"39.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"55.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"99 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"109 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start157 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK157 ft. MWL - Water Level, 10 %of cross sectional area157 ft. AMH - Downstream Manhole, Survey Begins - 01 0428157 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
76.2TF
125.1TF
130.4TF
117.4TFC
0MGOCONNECTION AT MH 3 O'CLOCK
157MGOCONNECTION AT MH 9 O'CLOCK
48TFC
2.1SAV
101.8TF
0MWL
0AMH01 0428
63.4TFC
58TFC
81.8TFC
150.8TF
0MWM
157AMH01 0429
157SAV
34.8TFC

Properties (6)

additional_info
SC306898
custom_field_two
3
customer
LACSD
datetime
2017-03-21T02:47:21-07:00
documentation
PROPIPE
is_lateral_inspection
false