Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2017, 11:08 AM
  • 01 0539_01 0538A_031017_035327.mp4

Date
03/10/2017
W/O
624605
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00206
PipeID
P01027
Time
3:08 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
4319
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_624605_TV01232_MAR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0539
Downstream MH
01 0538A
Dir. of Survey
Downstream
Length Surveyed
248.4 ft.
Total Length
248.4 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
147
O&M Index
2
O&M Quick
2I00
O&M Rating
98
Overall Index
3
Overall Quick
Overall Rating
245
Pipe schematic from manhole 01 0539 to 01 0538A
MH: 01 0539MH: 01 0538Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05393.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"41 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"65.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"78.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"96.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"128.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"137.5 ft. RPP - Repair Patch, from 09 to 12 o'clock, within 8 inches of joint: YES - ABS161.5 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"163.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"199.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"239.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"241 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"248.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0538A248.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish248.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish248.4 ft. MGO - General Observation - CONNECTION AT 9 O C

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Repair Patch, from 09 to 12 o'clock, within 8 inches of joint: YES - ABS

    137.5 ft. - Repair Patch, from 09 to 12 o'clock, within 8 inches of joint: YES - ABS

Observations (21)

DistanceCodeObservation
0MWM
248.4AMH01 0538A
248.4DAGS
248.4SAV
248.4MGOCONNECTION AT 9 O C
137.5RPPABS
199.6TF
163.7TF
241TF
96.4TF
78.3TF
0MWL
239.1TF
41TF
0AMH01 0539
65.9TF
3.6SAV
16TF
3.6DAGS
128.8TF
161.5TF

Properties (6)

additional_info
SC318732
custom_field_two
3
customer
LACSD
datetime
2017-03-10T03:08:51-08:00
documentation
PROPIPE
is_lateral_inspection
false