Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2017, 12:37 AM
  • 01 0540_01 0539_031017_033530.mp4

Date
02/17/2017
W/O
624605
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00206
PipeID
P01028
Time
4:37 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
4319
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_624605_TV01232_MAR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0540
Downstream MH
01 0539
Dir. of Survey
Downstream
Length Surveyed
311.3 ft.
Total Length
311.3 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
3
Overall Quick
Overall Rating
310
Pipe schematic from manhole 01 0540 to 01 0539
MH: 01 0540MH: 01 0539downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05400 ft. MWM - Water Mark, 20 %of cross sectional area2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start70.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"78.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"88.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"125.7 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"145.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"152.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"190.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"205.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"240.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"292.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"295.4 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"311.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish311.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0539311.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
205.1TFC
311.3DAGS
78.2TFC
311.3AMH01 0539
2.6DAGS
0MWL
152.8TF
295.4TF
2.6SAV
70.5TF
0AMH01 0540
190.3TF
125.7TF
240.2TF
0MWM
145.6TF
88.6TF
292.9TF
311.3SAV

Properties (6)

additional_info
SC318732
custom_field_two
3
customer
LACSD
datetime
2017-02-17T16:37:24-08:00
documentation
PROPIPE
is_lateral_inspection
false