Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 11, 2017, 06:18 AM
  • H 0716_H 0715_07102017_231959.mp4

Date
07/10/2017
W/O
640621
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00941
PipeID
P11124
Time
11:18 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4604
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_640621_TV15078_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0715
Downstream MH
H 0716
Dir. of Survey
Upstream
Length Surveyed
35.4 ft.
Total Length
35.4 ft.
Structural Index
2
Structural Quick
2700
Structural Rating
14
O&M Index
2
O&M Quick
2700
O&M Rating
14
Overall Index
2
Overall Quick
Overall Rating
28
Pipe schematic from manhole H 0715 to H 0716
MH: H 0715MH: H 0716upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - REVERSAL COMPLETE.33.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start33.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start35.4 ft. MWL - Water Level, 20 %of cross sectional area35.4 ft. MWM - Water Mark, 25 %of cross sectional area35.4 ft. AMH - Downstream Manhole, Survey Begins - H 0715

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2DAGS
0MWL
35.4DAGS
2SSS
0MWM
35.4SSS
0AMHH 0715
35.4MSAREVERSAL COMPLETE.

Properties (6)

additional_info
SC345436
custom_field_two
3
customer
LACSD
datetime
2017-07-10T23:18:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false