Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2017, 08:24 AM
  • H 0738_H 0737 _06292017_012458.mp4

Date
06/29/2017
W/O
640621
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00941
PipeID
P11147
Time
1:24 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4596
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
30
Purpose
Routine Assessment
Project
WO_640621_TV15078_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0738
Downstream MH
H 0737
Dir. of Survey
Downstream
Length Surveyed
790.1 ft.
Total Length
790.1 ft.
Structural Index
2
Structural Quick
2\00
Structural Rating
286
O&M Index
2
O&M Quick
2_00
O&M Rating
316
Overall Index
2
Overall Quick
Overall Rating
602
Pipe schematic from manhole H 0738 to H 0737
MH: H 0738MH: H 0737downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 07380 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.9 ft. MGO - General Observation - MAG COATING 65%75 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start790.1 ft. AMH - Downstream Manhole, Survey Ends - H 0737790.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish790.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    75 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
790.1AMHH 0737
2DAGS
0MWL
0AMHH 0738
75SSS
0MWM
5.9MGOMAG COATING 65%
790.1DAGS
790.1SSS

Properties (6)

additional_info
SC345422
custom_field_two
3
customer
LACSD
datetime
2017-06-29T01:24:38-07:00
documentation
PRO PIPE
is_lateral_inspection
false