Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2017, 09:19 AM
  • 15 0113_15 0112 _28062017_023022.mp4

Date
06/28/2017
W/O
624421
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12010
Time
2:19 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4595
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_624421_TV15037_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0113
Downstream MH
15 0112
Dir. of Survey
Downstream
Length Surveyed
168.4 ft.
Total Length
168.4 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
99
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
3
Overall Quick
Overall Rating
165
Pipe schematic from manhole 15 0113 to 15 0112
MH: 15 0113MH: 15 0112downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 01130 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start57.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"60.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"166.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish166.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish168.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK168.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE168.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0112

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
57.3TFC
60.7TFC
2SAV
2DAGS
168.4MGOCONNECTION AT MH 3 O'CLOCK
108.4TFC
0AMH15 0113
0MWL
168.4MGOCOCKROACHES IN MANHOLE
166.1SAV
0MGOCOCKROACHES IN MANHOLE
166.1DAGS
0MWM
168.4AMH15 0112
162.9TFC

Properties (6)

additional_info
SC345421
custom_field_two
3
customer
LACSD
datetime
2017-06-28T02:19:09-07:00
documentation
PRO PIPE
is_lateral_inspection
false