Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2017, 07:52 AM
  • 15 0119_15 0118 _28062017_011603.mp4

Date
06/28/2017
W/O
624421
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12016
Time
12:52 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4595
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_624421_TV15037_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0118
Downstream MH
15 0119
Dir. of Survey
Upstream
Length Surveyed
374.7 ft.
Total Length
374.7 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
216
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
366
Pipe schematic from manhole 15 0118 to 15 0119
MH: 15 0118MH: 15 0119upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 15 01199.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"24 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"94.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"146.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"225.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"349.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"362.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start362.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"372.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start372.9 ft. MGO - General Observation - MAG COATING 70%374.7 ft. MWM - Water Mark, 15 %of cross sectional area374.7 ft. MWL - Water Level, 10 %of cross sectional area374.7 ft. AMH - Downstream Manhole, Survey Begins - 15 0119374.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
0MWM
152.5TFA
301.3TF
12.5SAV
154.9TFA
1.8MGOMAG COATING 70%
374.7DAGS
365.2TF
374.7SAV
0MWL
25.1TFA
279.8TFA
0AMH15 0119
228.5TF
2DAGS
374.7MGOCOCKROACHES IN MANHOLE
350.7TFA
149.3TFA
374.7AMH15 0119
12.5TFA
0MGOCOCKROACHES IN MANHOLE
106.9TFC

Properties (6)

additional_info
SC345421
custom_field_two
3
customer
LACSD
datetime
2017-06-28T00:52:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false