Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2017, 08:20 AM
  • 15 0139_15 0138 _20062017_013319.mpg

Date
06/20/2017
W/O
624421
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00634
PipeID
P12038
Time
1:20 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4622
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_624421_TV15037_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0138
Downstream MH
15 0139
Dir. of Survey
Upstream
Length Surveyed
318.6 ft.
Total Length
318.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0138 to 15 0139
MH: 15 0138MH: 15 0139upstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 15 01391.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish66.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"93.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"171.5 ft. TFI - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 6", 1"238.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"316.2 ft. MGO - General Observation - MAG COAT316.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start318.6 ft. MWL - Water Level, 5 %of cross sectional area318.6 ft. MWM - Water Mark, 15 %of cross sectional area318.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK318.6 ft. AMH - Downstream Manhole, Survey Begins - 15 0138

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    147.1 ft. - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

Observations (13)

DistanceCodeObservation
0MWL
316.8SAV
0MWM
318.6MGOCONNECTION AT MH 3 O'CLOCK
2.4MGOMAG COAT
225.2TFC
251.7TF
2.4SAV
0MGOCONNECTION AT MH 3 O'CLOCK
147.1TFI
80.3TF
0AMH15 0138
318.6AMH15 0139

Properties (6)

additional_info
SC345337
custom_field_two
3
customer
LACSD
datetime
2017-06-20T01:20:06-07:00
documentation
PROPIPE
is_lateral_inspection
false