Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 27, 2017, 09:01 AM
  • 15 0122_15 0121 _27062017_021725.mp4

Date
06/27/2017
W/O
624421
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12020
Time
2:01 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4594
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_624421_TV15037_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0121
Downstream MH
15 0122
Dir. of Survey
Upstream
Length Surveyed
335.4 ft.
Total Length
335.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 15 0121 to 15 0122
MH: 15 0121MH: 15 0122upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 01222.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish2.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE24.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"37.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"104.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"161.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"213.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"333.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start333.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start335.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE335.4 ft. MWL - Water Level, 10 %of cross sectional area335.4 ft. AMH - Downstream Manhole, Survey Begins - 15 0121335.4 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
231.1TFC
2DAGS
119.2TFC
2SAV
121.7TF
0MWL
333.1SAV
295.3TFC
297.6TB
333.1DAGS
310.6TFA
335.4AMH15 0122
0AMH15 0121
174TF
49.9TFC
333.1MGOCOCKROACHES IN MANHOLE
0MWM

Properties (6)

additional_info
SC345342
custom_field_two
3
customer
LACSD
datetime
2017-06-27T02:01:41-07:00
documentation
PRO PIPE
is_lateral_inspection
false