Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2017, 09:13 AM
  • 15 0135_15 0134 _20062017_022556.mpg

Date
06/20/2017
W/O
624421
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00634
PipeID
P12034
Time
2:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4622
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_624421_TV15037_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0135
Downstream MH
15 0134
Dir. of Survey
Downstream
Length Surveyed
323.1 ft.
Total Length
323.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0135 to 15 0134
MH: 15 0135MH: 15 0134downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01350 ft. MWL - Water Level, 5 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT122.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES123.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"232.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES233.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"323.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish323.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0134323.1 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 09 o'clock,  , within 8 inches of joint: YES

    122.7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    232.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
122.7DAGS
2.1SAV
323.1SAV
233.8TFA
323.1AMH15 0134
232.4DAGS
323.1MGOCONNECTION AT MH 12 O'CLOCK
0MWM
0AMH15 0135
2.1MGOMAG COAT
0MWL
123.3TFA

Properties (6)

additional_info
SC345337
custom_field_two
3
customer
LACSD
datetime
2017-06-20T02:13:12-07:00
documentation
PROPIPE
is_lateral_inspection
false