Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 27, 2017, 10:46 AM
  • 15 0120_15 0119 _27062017_040243.mp4

Date
06/27/2017
W/O
624421
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12017
Time
3:46 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4594
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_624421_TV15037_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0119
Downstream MH
15 0120
Dir. of Survey
Upstream
Length Surveyed
377.2 ft.
Total Length
377.2 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
219
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
369
Pipe schematic from manhole 15 0119 to 15 0120
MH: 15 0119MH: 15 0120upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 15 01201.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish1.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE81.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"157.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"239.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"245.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"291.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"300.8 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"322.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"365.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start375.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start377.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE377.2 ft. MWM - Water Mark, 15 %of cross sectional area377.2 ft. MWL - Water Level, 10 %of cross sectional area377.2 ft. MGO - General Observation - 80% MAG COATING377.2 ft. AMH - Downstream Manhole, Survey Begins - 15 0119

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
54.9TFC
137.5TFA
86TFA
377.2MGOACTIVE CONNECTION AT MH 3 O'CLOCK
219.7TBA
229.6TFC
0MWM
376DAGS
11.6SAV
295.7TBA
376SAV
2DAGS
0MWL
376MGOCOCKROACHES IN MANHOLE
0MGO80% MAG COATING
131.8TFA
185.7TFC
377.2AMH15 0120
0AMH15 0119
76.4TBA

Properties (6)

additional_info
SC345342
custom_field_two
3
customer
LACSD
datetime
2017-06-27T03:46:11-07:00
documentation
PRO PIPE
is_lateral_inspection
false