Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2017, 10:36 AM
  • 15 0111_15 0110 _28062017_034950.mp4

Date
06/28/2017
W/O
624421
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12008
Time
3:36 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4595
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_624421_TV15037_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0111
Downstream MH
15 0110
Dir. of Survey
Downstream
Length Surveyed
200.9 ft.
Total Length
200.9 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
54
O&M Index
2
O&M Quick
312G
O&M Rating
83
Overall Index
2
Overall Quick
Overall Rating
137
Pipe schematic from manhole 15 0111 to 15 0110
MH: 15 0111MH: 15 0110downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 01110 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 8 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10.7 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS58.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"61.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start155.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"200.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0110200.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish200.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK200.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish200.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  15 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - DEBRIS

    10.7 ft. - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    109.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0AMH15 0111
10.7DSZDEBRIS
0MWL
200.9AMH15 0110
109.8TFC
106.8TFC
61.3TFC
200.9SAV
155.6TFC
2DAGS
159.3TFC
0MGOACTIVE CONNECTION AT MH 8 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
200.9MGOACTIVE CONNECTION AT MH 9 O'CLOCK
58.1TFC
200.9DAGS
109.8SAV
200.9MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC345421
custom_field_two
3
customer
LACSD
datetime
2017-06-28T03:36:47-07:00
documentation
PRO PIPE
is_lateral_inspection
false