Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 4, 2017, 08:12 AM
  • A 0311_A 0310_842017_013127.mp4

Date
08/04/2017
W/O
0636060
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08221
Time
1:12 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0607
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
20170804MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
A 0311
Downstream MH
A 0310
Dir. of Survey
Downstream
Length Surveyed
9.2 ft.
Total Length
9.2 ft.
Structural Index
4
Structural Quick
5141
Structural Rating
11
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
16
Pipe schematic from manhole A 0311 to A 0310
MH: A 0311MH: A 0310downstream0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:25AM0 ft. MWL - Water Level, 75 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING,PEELING CONCRETE6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR9 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish9 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish9 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish9.2 ft. MSA - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observation photos (4)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING,PEELING CONCRETE

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING,PEELING CONCRETE

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    6 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Survey Abandoned - DOWNLEG UPSTREAM SIPHON

    9.2 ft. - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observations (10)

DistanceCodeObservation
9.2MSADOWNLEG UPSTREAM SIPHON
9SAM
0MWM
0AMH1:25AM
6SRVCIRCUM REBAR
0MWL
9SSS
2SAMSEVERE AGG
2SSSBLISTERING,PEELING CONCRETE
9SRV

Properties (7)

additional_info
DOWNLEG UPSTREAM SIPHON
custom_field_three
CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2017-08-04T01:12:51-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false