Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 30, 2017, 05:57 AM
  • 02 1887_02 1886_29112017_215820.mp4

Date
11/29/2017
W/O
674077
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01172
PipeID
P04251
Time
9:57 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5054
Sewer Name
02 DOUGLAS AVENUE RELOCATION TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_674077_TV02046_DEC2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
02 1886
Downstream MH
02 1887
Dir. of Survey
Upstream
Length Surveyed
296.6 ft.
Total Length
296.6 ft.
Structural Index
3
Structural Quick
463K
Structural Rating
206
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
208
Pipe schematic from manhole 02 1886 to 02 1887
MH: 02 1886MH: 02 1887upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 18870.2 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish0.2 ft. MGO - General Observation - CONNECTION AT MH 1 O'CLOCK12.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.7 ft. RFL - Roots Fine Lateral, at 10 o'clock66.7 ft. RFC - Roots Fine Connection, at 09 o'clock66.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"82.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"97.3 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES115.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.2 ft. FM - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES141.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES151.2 ft. FM - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES158.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"161 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"176 ft. FM - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES206.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"225 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES251.9 ft. FM - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES259.7 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start259.8 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish272.2 ft. CL - Crack Longitudinal, at 07 o'clock, within 8 inches of joint: YES290.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"294.4 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start296.6 ft. AMH - Downstream Manhole, Survey Begins - 02 1886296.6 ft. MWM - Water Mark, 15 %of cross sectional area296.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK296.6 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (10)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 07 o'clock, within 8 inches of joint: YES

    24.4 ft. - Crack Longitudinal, at 07 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    36.9 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

    44.7 ft. - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    71.6 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    120.6 ft. - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

    145.4 ft. - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    155.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    169.4 ft. - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    199.3 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

Observations (30)

DistanceCodeObservation
145.4FM
0AMH02 1886
2.2SAV
36.9SAP
155.2FL
0MWM
5.9TF
122.9TF
199.3FM
120.6FM
213.7TF
36.8SAV
268.4TF
71.6FM
0MGOCONNECTION AT MH 9 O'CLOCK
296.6AMH02 1887
283.7TF
138.2TF
44.7FM
0MWL
296.4SAP
24.4CL
229.9RFL
229.8TF
296.4MGOCONNECTION AT MH 1 O'CLOCK
89.8TF
229.9RFC
135.6TF
181TF
169.4FM

Properties (6)

additional_info
SC346283
custom_field_two
2
customer
LACSD
datetime
2017-11-29T21:57:42-08:00
documentation
PROPIPE
is_lateral_inspection
false