Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2017, 11:24 AM
  • 22 1131_B 0720 _29112017_033620.mp4

Date
11/29/2017
W/O
674032
Weather
Dry
Operator/Surveyor
ERUIZ
Sewer ID
Z00110
PipeID
P09395
Time
3:24 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5147
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_674032_TV22155_DEC2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 1131
Downstream MH
B 0720
Dir. of Survey
Downstream
Length Surveyed
153.3 ft.
Total Length
153.3 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 22 1131 to B 0720
MH: 22 1131MH: B 0720downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 11317 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start9.4 ft. FM - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES29.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"78 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"126.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"149.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish153.3 ft. AMH - Downstream Manhole, Survey Ends - B 0720

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    9.4 ft. - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
0MWL
126.9TFC
7SAP
153.3AMHB 0720
149.3SAP
0MWM
78TFC
29.1TFC
9.4FM
0AMH22 1131

Properties (6)

additional_info
SC346457
custom_field_two
2
customer
LACSD
datetime
2017-11-29T03:24:31-08:00
documentation
PROPIPE
is_lateral_inspection
false